The Advantage of Smart Digital Sensors in Pharmaceutical Production

Purple Flower

When a batch deviation traces back to a measurement issue, the first questions asked are often about any sensors used in the production run. Do they all function correctly? Were any damaged? Are they even the right type for the job?

The most important questions center on whether a sensor was working exactly as designed, and yet still producing unreliable readings.

That needs to be determined because traditional sensors don’t usually fail in a dramatic manner. Rather, they tend to drift or degrade over time. And they certainly don’t give you a heads-up about when that’s starting to happen.

Clearly, this is a quality problem, but it’s also a compliance issue in the pharmaceutical industry. Let’s walk through this and see how smart digital sensors can help you maintain product quality and keep your facility compliant.

Measurements Are Vital Records

Analytical measurement shows up across basically every critical stage in pharmaceutical manufacturing:

  • pH governs fermentation control and buffer prep
  • Conductivity monitoring underlies Clean-In-Place/Sterilize-In-Place (CIP/SIP) validation and water for injection purity
  • Dissolved oxygen matters in bioreactor management
These are key parts of the process parameters that affect batch disposition and generate the records that support regulatory submissions and withstand inspection.

FDA inspectors take a careful look at measurement control programs. Sure, they’re concerned with whether calibration happened, but they’re also highly interested in knowing there’s a process in place that’s reliable, traceable, and consistently executed. Because of this, an up-to-date calibration log is a baseline expectation, and not the full story.

When an inspection finding points to measurement practices, the investigation tends to go well beyond any specific sensor in question. A 483 observation tied to calibration practices typically won’t close with just a corrective action for a single sensor. And it opens a broader question about how your facility reliably manages measurement across the board.

That will typically kick off a review of calibration procedures, documentation practices, training records, and whether the intervals used can be defended. This can make a long audit even longer.

It’s important to keep in mind that a sensor can pass a calibration check at a certain point in time, and still fail to deliver reliable measurements between then and the next calibration. So, how does that happen?

Three Ways Sensors Fail Without Obviously Failing

Sensors in pharmaceutical environments don’t always fail in ways that are easy to detect. They can degrade gradually and produce readings that still look plausible while drifting from the true process value. But in a highly regulated environment like yours, a plausible reading and an accurate one need to be the same. 

The thing is, sensor issues don’t happen randomly. They come from how traditional analog sensors are built and the specific demands the pharmaceutical industry places on them. That combination leads to three distinct types of failures.

1. Physical Failure

The first problem is physical failure. In these instances, traditional analog sensors are connected to their transmitters through a direct electrical coupling. The reference junction and cable connection sit exposed to whatever the process environment delivers.

In pharmaceutical applications, process environments include regular CIP/SIP cycles, which can come with caustic acid cleans, steam sterilization, and/or repeated temperature and pressure swings.

Over time, moisture finds its way into the connection, and corrosion takes place at the junction. The signal begins to gradually degrade, producing plausible readings on the display while no longer accurately reflecting the actual process. This all doesn’t happen overnight, which is partly why it’s so hard to catch.

2. Drift

Drift is a different kind of failure. All electrochemical sensors are prone to experiencing it, with slope and zero point shifting as the reference element ages, the electrolyte depletes, or the glass membrane wears down.

Between calibration intervals, that drift can be invisible. The sensor reports a number, but how far that number has moved from the true process value is unknowable without pulling it and checking. 

In fermentation or buffer prep, a pH reading that’s shifted from the true value can affect a process control decision with no immediately visible consequence. So, the batch looks normal, but the deviation will be seen later.

Conductivity monitoring adds a regulatory dimension to the same inherent problem.

USP <645> sets the standard for conductivity measurement in purified water and water used for injection. It specifies acceptable limits, calibration requirements, and the verification methods that make those measurements defensible. A sensor drifting between calibrations may produce readings that look compliant, even though the standard isn’t being met.

3. Human Error

The third type of failure is human. Manual calibration is innately variable. A technician calibrating the same sensor on Tuesday and again on Friday may get slightly different results following the exact same procedures.
Multi-shift operations can further compound this. 

If three technicians calibrate the same sensor loop during a week, there’s a lot that might not be captured in the record, especially if they’re on different shifts. What does get captured is that calibration occurred, but not necessarily any differences in their individual techniques. 

Across multiple sensors in a single facility, that variability can add up in ways that eventually pop up in batch records and audit findings.

These three failure modes don’t need anything to go obviously wrong. Instead, they usually happen in the background, throughout the course of normal pharmaceutical production. And that makes them costly to find. 

How Smart Digital Sensors Change the Picture

Something like M4 Knick’s Memosens digital technology can address each of those failures structurally. The connection and sensor architecture work differently in these products, which means the calibration is also different than analog sensors. And each difference addresses issues that can be found when you rely on traditional analog management.

For example, instead of a direct electrical coupling, Memosens uses an inductive connection between the sensor plug-in head and the cable. That means: 

  • There isn’t any metal-to-metal contact or exposed reference junction
  • Power and signal transfer inductively through a bayonet connector that locks securely and confirms its status on the transmitter display
  • The sensor head is hermetically sealed and rated for overpressure
  • CIP/SIP cycles and chemical cleans can’t compromise the signal path the way they can with an analog connection

In this case, the mechanism that allows moisture to enter and degrade a traditional sensor doesn’t exist, thereby avoiding a range of issues. Along with that, the sensor head also carries an integrated microprocessor that stores the sensor’s complete history (total operating hours, time logged under extreme conditions, full calibration records). 

Any compatible transmitter can read that history, so a technician doesn’t need to consult a paper log or query a separate system to know where a sensor is in its service life. The sensor carries that information, and when it moves from one process loop to another, the history moves with it.

With calibration moving to the lab, Memosens sensors can be conditioned, calibrated, and verified offline before they go into service. This takes any calibration event out of the process environment, standardizes it, and removes the variability that field calibration can introduce.

When you have a pre-calibrated sensor ready to go, there’s no calibration hold or wait for a new sensor to stabilize. That makes a huge difference for continuous processes.

Turn Schedule-Based Decisions Into Condition-Based Ones

The diagnostic data that Memosens provides changes how you make decisions about sensor replacement. The actual sensor condition starts driving the decision, and not simply a calendar date.

As you’re quite aware, traditional sensor management is calendar-based. When a sensor reaches its scheduled interval, it’s swapped out regardless of its actual condition. Sometimes, those sensors still have useful life remaining. Other times, they’ve already degraded beyond the point where a fixed schedule would’ve caught them. Clearly, neither of these situations is ideal.

But a smart digital sensor can display specific values that describe exactly where a sensor is in its service life. For example, Memosens provides:

  • Slope and zero point that indicate how the sensing membrane and reference element are performing relative to their original specs. A declining slope tells you that the electrode is becoming less responsive, and a shifting zero point indicates reference drift. Either can produce readings that look reasonable while being subtly wrong.
  • Response times that show you whether the membrane is still stabilizing as quickly as it should. Slowing response can indicate buildup or wear.
  • Glass impedance that reflects the membrane’s physical condition. Rising impedance can signal membrane dehydration or structural wear.

When your technician reads these values, they can distinguish between a sensor that needs to come out versus one that has service time remaining.

For your QA team, there’s an equally significant benefit to going with a smart digital sensor. The calibration history stored in the sensor head travels with the sensor for its entire service life. And those records are automatically timestamped, tied to the sensor’s identity, and accessible through any compatible transmitter.

This audit-ready documentation doesn’t depend on a logbook being filled out correctly, filed in the right place, or having to be found during an inspection. That can give your QA friends peace of mind.

Where to Start for Reliable Measurements

Getting reliable analytical measurement right takes three things:

  1. The sensors need to stay accurate
  2. The calibration process needs to be consistent
  3. The records need to hold up

Managing all three with an analog infrastructure that wasn’t designed to make any of them easy to verify is challenging (to say the least).

But ACI Controls works with pharmaceutical companies across the Northeast to evaluate measurement systems and identify where it makes sense to use smart digital technology like M4 Knick’s Memosens. 

That work draws on our familiarity and knowledge of how pharmaceutical facilities actually manage measurement programs. And it takes knowing which processes are best suited to digital sensors and where analog infrastructure is actually appropriate. 

When we talk, our conversation might be focused on a specific sensor loop that’s been causing problems, or perhaps we take a broader look at how calibration is managed across your facility. Either way, everything really starts with understanding your environment before we recommend anything.

If measurement reliability has been an issue for you, or if an audit or validation milestone is approaching, feel free to reach out to an ACI engineer. We can work with you to figure out what makes sense for your specific situation.

Tags

oil and gas filtration food industry compressed air condition monitoring power generation corrosion nitrogen generators safety connectors mettler toledo process control Cleaner Smarter and More Efficient Filtration Solutions Combustion Air Blowers Differential Pressure Temperature Transmitters hmi human machine interface ppe covid19 covid 19 prevent corrosion indoor air quality single ferrule tube fittings parker single ferrule compression fittings parker single ferrule fittings supercase ferrule hardening ferrules supercase compressed air filtration compressed air contamination parker compressed air filtration heat treat industrial heat treating food and beverage power industry sustainability combustion combustion types cement industry dust collection furnaces industrial furnaces plant efficiency energy management corrosion prevention moisture control electrical cabinets valves valve automation water treatment thermal oxidizer temperature control nitrogen generator energy efficiency digitization trends instrument gas supply column oil and gas industry all of the hidden costs of gas cylinders calibration equipment lifespan extending equipment lifespan sterile filtration trends compressed gas heat tracing water chilling compressed air filters manifolds robotics robotic technology robotics in manufacturing cost effective manufacturing lead reduce lead animal watering systems employee health improving employee health manufacturing productivity improvement drinking water thm thm analyzer parker thm water analyzer parker online thm analyzer apps manufacturing apps process improvement tubing plant safety safety tips leak free connections thermal mass flow magnetrol inline ball valves nsf ansi 61 nsfansi 61 back pressure back pressure safety valves safety valves streamline process condition monitoring process mixing materials compression fittings dissolved oxygen do measurement optical do sensors parker parker hannifin transmitters industrial transmitters smartline smartline transmitters downstream oil and gas oil and gas filtration industrial instrumentation process control instrumentation ph measurement ph measurement best practices ignition risk risk avoidance
Show All

Posts

2026
November October September August July June May April March February January
2025
October September August July June May April March February January
2024
July March January
2023 2022 2021 2020 2019
December November October September August July June May April March February January
2018
December November October September August July June May April March February January
2017